Back to Uttara Substation

TR-22 · Uttara Substation

Warning
Asset ID: TR-22Commissioned: 2005

Health Score

55/100

Elevated Stress

Current Load

90%

Elevated demand

Winding Temp

81 °C

Above threshold (75°)

Total Runtime

152,300 hrs

Continuous operation

Since Commissioning

21 Years

Late-life status

Winding Temperature — 30 Days

Max: 84°C · Avg: 77°C

Load Profile — 30 Days

Max: 95% · Avg: 84%

Oil Temperature — 30 Days

Max: 64°C · Avg: 59°C
AI Risk Assessment

Elevated Failure Risk

41% probability within 90 days

Contributing factors:

  • Load approaching rating
  • Elevated winding temperature
  • Age exceeds fleet median

→ Schedule thermal survey within 4 weeks

Maintenance History

  • Thermal survey — Completed2025-04-18

Fault History

  • Overcurrent trip — auto-reclosed2025-03-02
Pre-filled with asset TR-22 diagnosticsCreate Work Order